Exciter Model: ST3C

 

Model Equations and/or Block Diagrams

Parameters:

OEL OEL input: if < 2, add to error signal; if = 2, LV gate 1; if = 3, LV gate 2
UEL UEL input: if < 2, add to error signal; if = 2, HV gate 1; if = 3, HV gate 2
Tr Filter time constant, sec
ViMax Maximum error, pu
ViMin Minimum error, pu
Km DC converter gain
Tc Lag time constant, sec
Tb Lead time constant, sec
Ka Gain, pu
Ta Voltage regulator time constant, sec
Vrmax Maximum control element output, pu
Vrmin Minimum control element output, pu
Kg Excitation limiter gain, pu
Kp Potential source gain, pu
Ki Current source gain, pu
VbMax Maximum excitation voltage, pu
Kc Rectifier regulation factor, pu
Xl P-bar leakage reactance, pu
VgMax Maximum excitation voltage
ThetaPDeg Phase angle of potential source, degrees
Tm Time constant, sec
VmMax Model Parameters\VmMax
VmMin Model Parameters\VmMin
Kpr Proportional gain, pu
Kir Integral gain, pu
Vpidmax PID maximum limit
Vpidmin PID minimum limit
SW1 Logical switch 1 (1 = Position A, 2 = Position B)